Supervised Wiring
Use supervision with Alarms to detect cut and shorted wiring
This article is a guide for new Alarms. Refer to this article if you have classic Alarms. See New Alarms vs Classic Alarms if you are unsure which version of Alarms you have.
In an unsupervised circuit, a cut wire on a sensor wired normally open or a shorted wire on a sensor wired normally closed is not detected as an alarm trigger. Supervision enables the Verkada BP52 alarm panel to detect these events and trigger a notification or alarm.
Supervision types
The BP52 alarm panel supports 2 types of supervision:
Single End of Line Resistor (EOLR) (1 resistor)
Double EOLR (2 resistors)
These two types of supervision can be applied to sensors wired normally open (NO) or normally closed (NC). Reference resistance values for each type are shown below.
Single EOLR supervision (1000Ω resistors)
Resistance
Normally Closed (NC)
Normally Open (NO)
0 Ω
Shorted circuit; trouble condition
Shorted circuit or closed event; alarm activated
1000Ω
Normal state
Normal state
Infinite Ω
Cut wire or open event; alarm activated
Cut wire; trouble condition
Double EOLR supervision
Resistance
Normally Closed (NC)
Normally Open (NO)
0 Ω
Shorted circuit; trouble condition
Shorted circuit; trouble condition
1000Ω
Normal state
Closed event; alarm activated
2000Ω
Open event; alarm activated
Normal state
Infinite Ω
Cut wire; trouble condition
Cut wire; trouble condition
Wire EOLRs to your BP52 alarm panel
Resistors are installed at the end of the circuit, as close to the sensor as possible, for single and double EOL resistors. Installing EOL resistors at the panel inhibits the purpose of supervision.
Single EOLR
Double EOLR
Could not display content
Could not display content
It will not be compatible if you have a normally closed alarm sensor and the resistor is wired in parallel. If you have this configuration, add a single resistor in series to convert it to Double EOLR.

Need more help? Contact Verkada Support.
Last updated
Was this helpful?

