Configure Dry Lock on an AC41
Learn how to set up dry lock on an AC41 that does not lock or unlock as expected
If a lock stays continuously unlocked where an access power controller powers the lock, it may indicate that the power controller’s inputs require a normally open (NO) connection. This same issue can be seen with a power controller whose inputs are normally closed (NC). In this case, the lock remains continually locked and you can see the opposite results in the troubleshooting steps.
How to troubleshoot
If the lock state does not change as expected, you can verify that this problem is occurring:
Analysis
A ground loop is causing the access power controller to not detect the trigger events from the AC41.
Resolution
Use an isolator relay between the AC41 and the access power controller. This breaks the ground loop, causing the lock to unlock/lock, as expected. See example below:

Case Study
Issue
In a new access controller (AC41) deployment, one door would not lock. A grounding difference between the AC41 and the access power controller was to blame. This is typically referred to as a ground loop. To remedy the issue, a relay has been added between the AC41 and the access power controller inputs.
Troubleshooting steps
Assumptions
For this case study, there are 2 assumptions:
Assumption 1: The configuration is what was assumed to keep the door locked.
Assumption 2: The AC41’s lock relay may not be working.
Assumption 1
It was a standard dry setup for this lock.
The AC41’s normally open (NO) and common (COM) ports connect to the inputs on an access power controller.
The power controller supplies power to the maglock. See example below:

Assumption 2
The AC41’s lock relay may not be working. To troubleshoot, these are the steps tried:
The access power controller monitors its 2 inputs to see if it should unlock the maglock. It puts a voltage on an input and measures the voltage across an internal resistor to check. If the voltage is high, the power controller knows the connection between the two inputs is open. When we connect the inputs together the voltage is low triggering the unlock.

From our tests, the AC41 has the lock relay open, but the power controller detects a closed circuit.
The AC41 is able to supply power to the lock relay as many installs use the AC41 to power the lock. Due to this, the lock relay doesn’t act like a pure switch in a dry configuration. This relay connects to the AC41’s ground. This normally does not cause issues as the grounding of the AC41 and power controller match.
In this instance, the AC41 and the power controller had different earth grounds. This meant the reference voltage of AC41 did not match the power controllers. It’s the difference in potential that causes electricity to move. With a non-common ground, electricity moved from one ground to the other. This resulted in the power controller incorrectly detecting the input circuit as complete.

Resolution
We connected an isolator relay between the AC41 and the access power controller. This separated the devices to keep electricity from flowing from one ground to the other. Immediately after installing this relay, the maglock began to function as expected.
Here is the typical wiring for adding an isolator relay between the AC41 and an access power controller. You’d power the relay from the AC41 cassette, and then connect the common and NO or NC to the inputs on the power controller. Use NC if the power controller expects a normally closed circuit, and NO otherwise.
Wiring of the AC41 cassette to the relay

Diagram of the fix

Need more help? Contact Verkada Support.