Verkada Air Quality Sensors offer your organizations a way to monitor essential indoor air quality factors, such as CO2, CO, PM 2.5, PM 4.0, PM 10.0, AQI, TVOC, and formaldehyde.
The Building Automation and Control Networks (BACnet) integration allows Verkada sensors to inform a building’s Heating, Ventilation, and Air Conditioning (HVAC) system about an air quality metric or any sensor reading, allowing the building HVAC to respond to these indoor air quality conditions.
Verkada sensors can integrate with the Building Management System (BMS) protocol, BACnet. By integrating Verkada's sensors with this protocol, your organization's HVAC systems can now automatically respond to suboptimal air conditions. Learn more about BACnet for Verkada Air Quality Sensors.
To use this integration, your building must have a Building Automation System (BAS) that is compatible with BACnet IP. We recommend that you contact your HVAC specialist to understand if your system is supported. If you are unsure or need help, contact Verkada Support.
Enable BACnet for your org using the Feature Manager
To activate the BACnet functionality on your sensors, you first need to enable the BACnet feature for your organization.
In Verkada Command, go to All Products > Admin.
Select the Privacy & Security tab.
Click Feature Manager.
Under Air Quality, find Sensor BACnet and change it from Disable to Enable.
Enable BACnet on a Verkada sensor
Once the BACnet feature is enabled for your organization, you're ready to enable it on your devices. Learn more about BACnet for Verkada Air Quality Sensors.
In Verkada Command, go to All Products > Air Quality.
Click the sensor you want to enroll for BACnet.
At the top right, click the Settings icon (gear).
On the left, click BACnet. (If you don't see the BACnet option, ensure the device is an SV21, SV23, or SV25, and ensure BACnet is enabled for your organization.)
Click the dropdown and select Enable.
Assign a unique BACnet Device ID so you can identify your sensor on your BAS/BMS. The Device ID identifies the device on the BACnet network; therefore, each Verkada sensor should have a unique Device ID in the range of 0–4194302.
Assign a BACnet port. The default BACnet port is 47808, which is a commonly used UDP port for BACnet/IP, but it can also be any number in the range of 47808–47823. We recommend that the UDP port stay unchanged because the default value is mainly used.
Click Apply to save your changes.
BACnet should now be enabled on the device. Anything on the BACnet server can now poll the device for properties.
Disable BACnet on a Verkada sensor
In Verkada Command, go to All Products > Air Quality.
Click the sensor you want to disable BACnet for.
At the top right, click the Settings icon (gear).
On the left, click BACnet. (If you don't see the BACnet option, ensure the device is an SV21, SV23, or SV25, and ensure BACnet is enabled for your organization.)
BACnet PICS
BACnet Standardized Device Profile (Annex L)
Smart Sensor BIBB Device profile: B-SS
List all BACnet Interoperability Building Blocks Supported (Annex K)
Data sharing/device and network management services
DS-RP-B
DM-DDB-B
DM-DOB-B
Segmentation Capability
Segmented requests supported: No Window Size
Segmented responses supported: No Window Size
Standard object types supported
An object type is supported if it is present in the device.
Supported Models | Name | Object Type | Instance | Units |
SV23, SV25 | Vape Index | AnalogInput | 1 | No Units |
SV21, SV23, SV25 | Temperature (C) | AnalogInput | 2 | Degrees Celsius |
SV21, SV23, SV25 | Humidity | AnalogInput | 3 | % Relative Humidity |
SV21, SV23, SV25 | CO2 | AnalogInput | 4 | ppm |
SV25 | Carbon Monoxide | AnalogInput | 5 | ppm |
SV23, SV25 | Noise | AnalogInput | 6 | dB |
SV23, SV25 | AQI | AnalogInput | 7 | No Units |
SV23, SV25 | TVOC Index | AnalogInput | 8 | No Units |
SV23, SV25 | PM 2.5 | AnalogInput | 9 | μg/m^3 |
SV21, SV23, SV25 | Tamper | AnalogInput | 10 | No Units |
SV23, SV25 | Motion | AnalogInput | 11 | No Units |
SV25 | Light | AnalogInput | 12 | Lux |
SV25 | Pressure | AnalogInput | 13 | Hectopascal |
SV25 | Formaldehyde | AnalogInput | 14 | ppb |
SV23, SV25 | PM 4.0 | AnalogInput | 15 | μg/m^3 |
SV23, SV25 | PM 10.0 | AnalogInput | 16 | μg/m^3 |
Device
Object Type | ID | Object Name |
Device: | <user-specified-id-in-command> | <device-serial-number> |
Dynamically Creatable: No
Dynamically Deletable: No
Data Link Layer Options
BACnet IP, (Annex J)
Device Address Binding
Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and certain other devices.)
No
Character Sets Supported
Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
ISO 10646 (UTF-8)