# Verkada 공기질 센서를 위한 BACnet

Verkada [공기질 센서](https://docs.verkada.com/docs/air-quality-sensors-overview.pdf) 귀사의 조직이 다음을 포함한 필수 실내 공기질 요소를 모니터링할 수 있게 해줍니다 [CO2](https://help.verkada.com/air-quality/ko/sensor-data/air-quality-sensor-readings), [CO](https://help.verkada.com/air-quality/ko/sensor-data/air-quality-sensor-readings), [PM 2.5](https://help.verkada.com/air-quality/ko/sensor-data/air-quality-sensor-readings), [PM 4.0](https://help.verkada.com/air-quality/ko/sensor-data/air-quality-sensor-readings), [PM 10.0](https://help.verkada.com/air-quality/ko/sensor-data/air-quality-sensor-readings), [AQI](https://help.verkada.com/air-quality/ko/sensor-data/air-quality-sensor-readings), [TVOC](https://help.verkada.com/air-quality/ko/sensor-data/air-quality-sensor-readings), 그리고 [포름알데히드](https://help.verkada.com/air-quality/ko/sensor-data/air-quality-sensor-readings).

해당 [빌딩 자동화 및 제어 네트워크(BACnet)](https://www.ashrae.org/technical-resources/technical-faqs/question-51-what-is-bacnet) 통합을 통해 Verkada 센서는 건물의 난방, 환기 및 공조(HVAC) 시스템에 공기질 지표나 기타 센서 판독값을 전달할 수 있으며, 이를 통해 건물의 HVAC가 이러한 실내 공기질 조건에 대응할 수 있게 합니다.

Verkada 센서는 빌딩 관리 시스템(BMS) 프로토콜인 BACnet과 통합할 수 있습니다. Verkada의 센서를 이 프로토콜과 통합하면 귀사의 HVAC 시스템이 이제 최적이 아닌 공기 상태에 자동으로 대응할 수 있습니다. 다음 방법을 알아보세요 [Verkada 공기질 센서에 BACnet 구성하기](https://help.verkada.com/air-quality/ko/configuration/bacnet-for-verkada-air-quality-sensors/configure-bacnet-on-air-quality-sensors).

***

## BACnet 소개

BACnet은 건물 자동화 및 제어 시스템을 위해 특별히 설계된 통신 프로토콜입니다. HVAC, 조명, 보안 및 기타 건물 자동화 시스템과 같은 건물 내 장치와 시스템 간에 데이터를 교환하는 데 사용되는 산업 표준 프로토콜입니다.

BACnet은 서로 다른 제조업체의 다양한 장치와 시스템이 기본 하드웨어나 소프트웨어 구현과 관계없이 서로 통신할 수 있는 표준화된 방법을 제공합니다.

BACnet의 목표는 건물 자동화 장치 간의 효율적이고 표준화된 통신을 가능하게 하여, 건물 제어 시스템의 설계 및 운영에서 상호 운용성, 확장성, 유연성을 촉진하는 것입니다.

***

## BACnet의 이점

다음은 BACnet의 직관성이 귀사에 유익할 수 있는 몇 가지 사례입니다:

* 비용 절감을 위해 실내 또는 건물의 온도를 조절합니다
* 실내의 신선한 공기 순환을 늘리기 위해 댐퍼 출력을 조절합니다
* 공급 팬을 켭니다
* 공기질이 나쁠 때 창문을 자동으로 닫습니다
* CO2 수준이 높을 때 공기 여과 시스템을 자동으로 켜고 외부 공기 유량을 늘립니다
* 공기가 깨끗할 때 불필요한 여과를 피하기 위해 오염 임계값에 도달한 경우에만 공기를 여과 시스템으로 통과시킵니다
* VOC 수치가 높을 때 실험실의 환기율을 자동으로 높입니다
* 다음을 사용합니다 [SV23](https://docs.verkada.com/docs/air-quality-sensors-overview.pdf) 및 [SV25](https://docs.verkada.com/docs/air-quality-sensors-overview.pdf) 를 점유 센서로 사용하여, 방이 비어 있을 때 HVAC 시스템의 작동을 줄이도록 설정된 경우 HVAC 에너지 비용을 절감합니다
* 다음을 사용합니다 [SV25](https://docs.verkada.com/docs/air-quality-sensors-overview.pdf) 점유되지 않았지만 빛이 감지될 때 방의 조명을 끕니다
* 베이핑이 감지되면 스트로브 또는 경보를 작동시킵니다

***

## BACnet 사용 사례

BMS(빌딩 자동화 시스템이라고도 함)가 BACnet을 지원하는 경우, Verkada 센서를 입력으로 사용하여 HVAC 장비나 BMS 내의 다른 장비를 제어할 수 있습니다.

BACnet은 중앙 집중식 제어와 모니터링을 가능하게 하며, 온도, 습도, PM 2.5, TVOC, CO2 등의 Verkada 센서 입력 값을 받아 영향 완화를 위한 출력 제어에 사용할 수 있습니다. 예를 들어, 회의실에 설치된 센서가 높은 CO2 경고를 발생시키면, 이 정보가 BAS/BMS로 전달되고, 이어서 회의실의 환기 팬이나 댐퍼 전원을 켜는 것과 같은 특정 동작을 제어할 수 있습니다.

***

## 구현 예시

**시나리오**: Verkada 공기질 센서가 회의실의 CO2를 모니터링하고 CO2가 700ppm에 도달하면 공기 흐름을 늘리도록 하려는 경우.

{% stepper %}
{% step %}
**Verkada 공기질 센서를 설치하고 BACnet 네트워크에 연결합니다.**
{% endstep %}

{% step %}
**장치에서 BACnet을 활성화하고 고유한 장치 ID를 부여합니다. 다음을 참조하세요** [**장치에서 BACnet을 활성화하는 방법**](#h_2d2ca08f93)**.**
{% endstep %}

{% step %}
**BACnet-over-IP 호환 BMS로 이동하여 "discover" 기능을 사용해 Verkada 센서를 찾습니다. 이 예에서는 Vykon WorkPlace N4를 사용합니다.**

<div align="left" data-with-frame="true"><img src="https://4289613663-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FJtgmyWYlTEX9DpjvBwTL%2Fuploads%2Fgit-blob-fd9d50cadad9e68ea06b41585b5bab03824c09b3%2F6b94c8262ff8c822caa8cfef838c007623a67d60.png?alt=media" alt=""></div>

이렇게 하면 네트워크에서 발견된 BACnet 장치가 반환됩니다.

<div align="left" data-with-frame="true"><figure><img src="https://4289613663-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FJtgmyWYlTEX9DpjvBwTL%2Fuploads%2F34tsEuxj5gigUcRGClO6%2Fbac.png?alt=media&#x26;token=aa4cd35b-ae1f-4d21-9962-41873319ef53" alt=""><figcaption></figcaption></figure></div>
{% endstep %}

{% step %}
**장치 이름을 변경하고 BMS에 추가합니다.**
{% endstep %}

{% step %}
**BACnet Who-Has 검색을 실행하여 사용 가능한 모든 포인트를 찾습니다.**

<div align="left" data-with-frame="true"><img src="https://4289613663-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FJtgmyWYlTEX9DpjvBwTL%2Fuploads%2Fgit-blob-1c2ea640a84a70088dc5f3b7d534337669157a5e%2Fa9115d3d1199859d819e7d8e4e5fb7d4f4fe39f1.png?alt=media" alt=""></div>
{% endstep %}

{% step %}
**포인트를 BMS에 추가하고 HVAC 결정을 내리는 데 사용합니다.**

<div align="left" data-with-frame="true"><img src="https://4289613663-files.gitbook.io/~/files/v0/b/gitbook-x-prod.appspot.com/o/spaces%2FJtgmyWYlTEX9DpjvBwTL%2Fuploads%2Fgit-blob-51af7f3175cd3fcd1a81cc3f7159b86fc102015d%2F54011e3800ce03b65114bdaeb9c14883591f96ee.png?alt=media" alt=""></div>

1. 이 경우, **In2** 는 SV25 CO2 판독값에 연결되며, 이는 **In A,** 로 전달되고, 이는 **GreaterThanEqual** 함수입니다.
2. 만약 **SV25 CO2** 판독값이 **700ppm**보다 높으면 **True**를 보내고, 그렇지 않으면 **False**.
3. 를 연결합니다 **Out** (해당 함수의 출력)을 BooleanWritable 변수의 입력에 연결합니다. 이 경우 **In16**. **In16** 가 **Out** boolean을 결정합니다.
4. 를 연결합니다 **Out** boolean을 댐퍼 제어에 사용합니다.
   1. 만약 **Out** 가 True이면 댐퍼는 **열림**.
   2. 만약 **Out** 이 **False**, 댐퍼는 **닫힘**.
      {% endstep %}
      {% endstepper %}

***

## FAQ

<details>

<summary>모든 BMS/BAS가 BACnet을 사용하나요?</summary>

아니요, 모든 빌딩 관리 시스템(BMS)/빌딩 자동화 시스템(BAS)이 BACnet을 지원하는 것은 아닙니다. 대부분의 주요 HVAC 공급업체는 이 기능을 지원하는 제품과 컨트롤러를 보유하고 있습니다. 하지만 귀하의 시스템이 지원되는지 확인하려면 HVAC 전문가와 상담해야 합니다.

{% hint style="danger" %}
이 통합을 사용하려면 귀하의 건물에 BACnet IP와 호환되는 BAS가 있어야 합니다. 시스템이 지원되는지 확인하려면 HVAC 전문가에게 문의하는 것이 좋습니다. BAS가 BACnet을 지원하는지 확실하지 않은 경우, 다음에 संपर्क하세요 [Verkada 지원팀](https://www.verkada.com/contact/) 에 추가 지원을 요청하세요.
{% endhint %}

</details>

<details>

<summary>BACnet에서 지원되는 센서 판독값은 무엇인가요?</summary>

모든 Verkada [센서 판독값](https://help.verkada.com/air-quality/ko/sensor-data/air-quality-sensor-readings) 을 BMS의 입력으로 사용할 수 있습니다. 예를 들면 [온도](https://help.verkada.com/air-quality/ko/sensor-data/air-quality-sensor-readings), [습도](https://help.verkada.com/air-quality/ko/sensor-data/air-quality-sensor-readings), [CO2](https://help.verkada.com/air-quality/ko/sensor-data/air-quality-sensor-readings) 값, [베이프 지수](https://help.verkada.com/air-quality/ko/readme)등을 사용하여 댐퍼, 환기 팬 또는 기타 HVAC 장비를 제어할 수 있습니다.

</details>

<details>

<summary>Verkada 센서가 HVAC를 직접 제어하나요?</summary>

아니요, Verkada 센서는 건물의 HVAC 시스템을 직접 제어하지 않습니다. 대신 센서는 판독값을 BMS로 전달하고, BMS는 이를 건물의 HVAC를 제어하는 함수의 입력으로 사용합니다. 예를 들어 실내 온도를 조절하거나 밀폐된 공간의 공기 흐름을 늘리는 방식입니다.

</details>

<details>

<summary>Verkada 공기질 모니터는 BACnet MS/TP를 지원하나요?</summary>

아니요, BACnet Master Slave(MS)/Token Passing(TP)은 RS-485 [연결이 필요한 유선 버전의 BACnet으로, 당사의 출입 통제 리더와 유사하지만 현재 Verkada 공기질 센서는 지원하지 않습니다. 추가 정보나 지원이 필요하시면 SE에 문의하세요.](https://en.wikipedia.org/wiki/RS-485) 합니다.

</details>

<details>

<summary>BACnet을 활성화하면 어떤 일이 일어나나요?</summary>

장치에서 BACnet이 활성화되면 BMS 컨트롤러는 이제 BACnet 네트워크에서 해당 장치를 "discover"할 수 있습니다. 그렇기 때문에 BACnet 장치에는 장치 ID가 필요하며, 이는 네트워크에서 장치를 식별하는 데 사용되고, 포트 또한 통신에 사용됩니다. 서버는 "Who-Is/I-Am" 흐름을 통해 장치와 핸드셰이크를 시작합니다. 그런 다음 "Who-Has/I-Have" 흐름을 통해 장치가 어떤 속성을 가지고 있는지 확인합니다.

{% hint style="warning" %}
Verkada [SV21](https://docs.verkada.com/docs/air-quality-sensors-overview.pdf), [SV23](https://docs.verkada.com/docs/air-quality-sensors-overview.pdf), 그리고 [SV25](https://docs.verkada.com/docs/air-quality-sensors-overview.pdf) 는 모두 BACnet/IP 프로토콜을 지원하며 IPv4를 지원합니다. UDP 포트의 기본값은 47808(0xBAC0)입니다.
{% endhint %}

</details>