Supervised Wiring for Access Control
Learn how supervision allows a Verkada access controller to detect cut and shorted wiring
Supervision enables all second-generation or newer access control products to detect if a REX or DPI wired normally open (NO) has been cut or if a wire configured normally closed (NC) has been shorted and trigger a notification, aux output event, or raise an alarm if set as a Verkada Alarms trigger. We also support supervised wiring for alarms which is configured and used separately.
Supervision types
Most access controllers support single end-of-line (EOL) and double EOL supervision. These 2 types of supervision can be applied to REX and DPI sensors wired normally open (NO) or normally closed (NC). The resistors should be placed as closely to the devices as possible to prevent a short or cut in the wire at the end of the line.
Single EOLR supervision
Resistance
Normally Closed (NC)
Normally Open (NO)
0 Ω
Shorted circuit; trouble condition
Shorted circuit or closed event; alarm activated
1000Ω
Normal state
Normal state
Infinite Ω
Cut wire or open event; alarm activated
Cut wire; trouble condition
Double EOLR supervision
Resistance
Normally Closed (NC)
Normally Open (NO)
0 Ω
Shorted circuit; trouble condition
Shorted circuit; trouble condition
1000Ω
Normal state
Closed event; alarm activated
2000Ω
Open event; alarm activated
Normal state
Infinite Ω
Cut wire; trouble condition
Cut wire; trouble condition
Wire EOL resistors to your access controller
The resistors should always be installed at the end of the circuit, as close to the sensor as possible. Installing EOL resistors at the panel can inhibit the purpose of supervision.
Single EOLR Double EOL


Setting up EOL resistors in Command
In Verkada Command, go to All Products > Access.
Select a site from the All Sites dropdown.
Select a door and click Settings .
Under Hardware, select where the EOL resistor is located. Supervised wiring can be configured under the following sections:
a. DPI b. REX1 c. REX2
Next to the Supervised Wiring dropdown, select the correct EOL resistor for the door.

Event tiles for supervised events will appear automatically once enabled.